Description:

FULL INSPECTION

Outstanding Inspections

Case Number: T10FR01048
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/27/2010 INSP - FULL JDAVIS Correction Required 1. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed: - SPRINKLER SYSTEM SHALL BE EXTENDED TO MAINTAIN COVERAGE IN THE RISER ROOM - A SIGN SHALL BE PROVED STATING "RISER ROOM" 2. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated: - REPLACE THE CEIILNG TILES AND GRID SYSTEM IN THE RISER ROOM