Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

05/27/2010

Applicant:

MASSAPEQUA ASSOCIATES LLC

Description:

Full Fire Prevention Inspection. Angel Yordan 622-2854

Outstanding Inspections

Case Number: T10FR01040
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
05/27/2010 INSP - FULL JBURGE Correction Required Please correct all noted Tucson Fire Code violations.
05/27/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the locking bar and hardware from the East egress door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg