Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

05/27/2010

Applicant:

26 PALMS DELAWARE LLC & SIERRA INDUSTRIAL

Description:

FULL INSPECTION

Outstanding Inspections

Case Number: T10FR01038
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/27/2010 INSP - FULL JDAVIS Correction Required 1. _____ 1028.6 Panic Hardware. Where panic hardware is installed, the panic or fire exit hardware shall be the only locking device on the door... - Currently there is a bar accross both rear exits that are alo supplied with a pad lock. This is prohibited. 2. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied - Ladies bathroom - outside the bar leading from the kitchen 3. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: - Place blanks in the electrical panel 4. _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. - In Storage Room 5. _____ 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. - Replace the missing electrica lcoverplaters: *Behind the microwave *In the O.T.B. romm 6. _____ 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. - Currently the sprinklered awning has an extension with does not have sprnkler coverage. 7. _____ 1008.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. - Currently the East gate serving the East exit does not meet the same standard as the door it serves. The gate must be provided with a thumb-latch locking device Note: Occupant lad card is posted. O.L=250