Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/20/2010

Applicant:

MC DONALD S CORPORATION

Description:

McDonalds fire inspection.

Outstanding Inspections

Case Number: T10FR01013
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
05/20/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
05/20/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
05/20/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. ____ Extend sprinkler coverage for the remodeled areas in the basement and inside walk-in coolers.
05/20/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.11.6.3 - Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
05/20/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
05/20/2010 VIOL - COMPRESSED GASES JLOYA Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR01013
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/20/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
12/22/2010 INSP - REINSPECTION JLOYA Approved Violations abated