Case: T10FR01007
Case Details
Entered Date:
05/19/2010
Applicant:
ALBRIGHT MERLYN D & DONITA R TR
Description:
Full Fire Prevention Inspection. John White 971-7873
Outstanding Inspections
Case Number: T10FR01007
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2010 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. _____1. Replace all missing ceiling tiles. |
05/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service, mount and tag all portable fire extinguishers. |
05/19/2010 | VIOL - HAZARDOUS MATERIALS,GEN | JBURGE | Correction Required | IFC 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____1. Post hazard identification signs on all sides of the building. |
05/19/2010 | VIOL - LIQUID PETROLEUM GASES | JBURGE | Correction Required | IFC 3804.3 Container location. Containers shall be located with respect to buildings, public ways, and lot lines of adjoining property that can be built upon, in accordance with Table 3804.3. _____1. The propane tank shall be located at least 10 freet from the building and all combustible material. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR01007
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |