Case: T10FR00908
Case Details
Entered Date:
05/05/2010
Applicant:
AGRO LAND & CATTLE CO INC
Description:
Silhouette Photography 5/3/10
Outstanding Inspections
Case Number: T10FR00908
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2010 | VIOL - FIRE SERVICE FEATURES | MPursley | Correction Required | 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____Remove door knob on extra bathroom door. _____Place "Not an Exit" sign on extra doors, including back door. |
| 05/05/2010 | VIOL - BUILDING SVCS & SYSTEMS | MPursley | Correction Required | 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00908
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2010 | INSP - REINSPECTION | MPursley | Approved | All corrections made 5/27/10 |