Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

05/05/2010

Applicant:

AGRO LAND & CATTLE CO INC

Description:

Silhouette Photography 5/3/10

Outstanding Inspections

Case Number: T10FR00908
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
05/05/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____Remove door knob on extra bathroom door. _____Place "Not an Exit" sign on extra doors, including back door.
05/05/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00908
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/28/2010 INSP - REINSPECTION MPursley Approved All corrections made 5/27/10