Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR00893
Case Details
Entered Date:
05/04/2010
Applicant:
MARSHALL FOUNDATION
Description:
Deficiencies - CINTAS
Outstanding Inspections
Case Number: T10FR00893
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2010 | INSP - FULL | EGriffin | Violation | Currently the fire suppression report for the kitchen extinguishing system indicates the system interconnection to the fire suppression system does NOT include all appliances or cooking equipment. This must be corrected or equipment shall be removed. SEE REPORT. The following Tucson Fire Code states: 904.3.3 System interlocking. Automatic equipment interlocks with fuel shutoffs, ventilation controls, door closers, window shutters, conveyor openings, smoke and heat vents, and other features necessary for proper operation of the fire-extinguishing system shall be provided as required by the design and installation standard utilized for the hazard. Report shall be re-submitted and WITH all deficiencies corrected. |