Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/29/2010

Applicant:

FIMBRES JORGE H & GLORIA G CP/RS

Description:

El tingon tire shop fire inspection.

Outstanding Inspections

Case Number: T10FR00862
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/29/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
04/29/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
04/29/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
04/29/2010 VIOL - TIRE REBUILDING/STORAGE JLOYA Violation 2505.4 Distance from lot lines and buildings. Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings. Exception #1: For existing storage before August 4, 2004 individual piles not exceeding 5,000 square feet (464.5m²) of continuous area shall be located 10 feet (3048.3 mm) from buildings and lot lines for storage not exceeding 6 feet (1829 mm) in height. Exception #2: For existing storage before August 4, 2004 individual piles exceeding 6 feet (1829 mm) in height shall be located 20 feet (6096.6 mm) from buildings and lot lines.
04/29/2010 VIOL - HAZARDOUS MATERIALS,GEN JLOYA Violation 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere. ___ Provide secondary containment for waste oil container.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00862
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/29/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
06/23/2010 INSP - REINSPECTION JLOYA Approved All violations abated.