Case: T10FR00852
Case Details
Entered Date:
04/28/2010
Applicant:
MASSAPEQUA ASSOCIATES LLC
Description:
Full Fire Prevention Inspection Keri Mullane
Outstanding Inspections
Case Number: T10FR00852
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service all portable fire extinguishers. _____2. Service the kitchen hood extinguishing system. |
| 04/28/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the kitchen hood system. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 04/28/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located in the dinning area by the yellow wing. _____2. Repair or replace the emergency lighting unit located in the womens restroom. _____3. Repair or replace the emergency lighting unit located on the North wall by the East Exit door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00852
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |