Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/22/2010

Applicant:

GENERAL DENTISTRY REAL ESTATE LLC

Description:

Check center fire inspection.

Outstanding Inspections

Case Number: T10FR00792
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/22/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/22/2010 VIOL - EMERGENCY PLAN/PREPARE JLOYA Violation 407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises.
04/22/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ___Cover open slots at electrical panel.
04/22/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
04/22/2010 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.
04/22/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00792
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/06/2010 INSP - REINSPECTION JLOYA Approved All violations abated.