Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

04/22/2010

Applicant:

DEVELOPMENT TRADING AND TRANSACTING

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T10FR00789
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/22/2010 INSP - FULL WMOTTO Correction Required CORRECT TUCSONFIRE CODE VIOLATIONS.
04/22/2010 VIOL - BUILDING SVCS & SYSTEMS WMOTTO Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1___ NEED BLANKS INTALLED IN ELECTRICAL PANNELS WITH OPEN SLOTS IN KITCHEN NEAR EXIT DOOR.
04/22/2010 VIOL - COMPRESSED GASES WMOTTO Correction Required 3003.5.1 Security of areas. Areas used for the storage, use and handling of compressed gas containers, cylinders, tanks and systems shall be secured against unauthorized entry and safeguarded in an approved manner. 1___SECURE ALL GAS CYLINDERS WITH CHAIN OR CORD TO WALL TO PREVENT FROM FALLING.