Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/22/2010

Applicant:

3200 N FIRST AVENUE LTD PARTNERSHIP

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T10FR00788
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
04/22/2010 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ HOOD SYSTEM NEEDS TO BE TAGGED AND SERVICED EVERY SIX MONTHS.
04/22/2010 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Correction Required 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained. 1___ ALL EXTINGUISHERS NEED TO BE TAGGED AND SERVICED EVERY YEAR. 2___ CLASS K EXTINGUISHER IN KITCHEN NEEDS TO BE TAGGED AND SERVICED.
04/22/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1___ REMOVE LATCH LOCK ON REAR EXIT DOOR IN KITCHEN. 2___ REMOVE KEYED DEADBOLTS ON METAL PATIO DOORS. REPLACE WITH A THUMB TURN DEAD BOLT.
04/22/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. 1___ NEED SIGN OVER MAIN ENTRANCE DOOR STATING THESE DOOR TO REMAIN UNLOCKED DURING BUISNESS HOURS.
04/22/2010 VIOL - MEANS OF EGRESS WMOTTO Correction Required 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___REPAIR EXIT SIGN OVER REAR KITCHEN DOOR.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00788
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/08/2010 INSP - FULL WMOTTO Approved ALL VIOLATIONS ABATED.