Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/21/2010

Applicant:

BM VALENCIA LLC

Description:

Valencia Jiffy lube fire inspection.

Outstanding Inspections

Case Number: T10FR00780
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/21/2010 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.
04/21/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4.2 - Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle.
04/21/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00780
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
04/21/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
05/06/2010 INSP - REINSPECTION JLOYA Approved All violations abated.