Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/19/2010

Applicant:

TUCSONIC OPERATING COMPANY

Description:

Full Fire Prevention Inspection. Tammy Tague

Outstanding Inspections

Case Number: T10FR00764
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/19/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Replace the missing hood system filters. _____2. Service and tag the portable fire extinguisher.
04/19/2010 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the double keyed locks from the two south doors and replace them with thumb-turn locks. NOTE: The panic hardware on the south door is not required and can be removed. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
04/19/2010 VIOL - COMPRESSED GASES JBURGE Correction Required IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Secure the CO2 cylinder located in the kitchen with a chain or strap to prevent falling.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00764
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/26/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.