Case: T10FR00763
Case Details
Entered Date:
04/19/2010
Applicant:
MC DONALDS CORPORATION
Description:
Full Fire Prevention Inspection. Angel Torres 798-3445
Outstanding Inspections
Case Number: T10FR00763
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/19/2010 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | IFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1. Maintain 24 inches of clearance between the ceiling and the top of the dry storage located in the kitchen. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 04/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the kitchen hood extinguishing systems. _____2. Service and tag all portable fire extinguishers. |
| 04/19/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The south EXIT sign located in the play area shall be repaired and shall be fully illuminated. _____2. The east EXIT sign located in the play area shall be illuminated. _____3. The EXIT sign located in the dry storage area shall be fully illuminated. |
| 04/19/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located in the side lobby. _____2. Repair or replace both emergency lighting units located in the play area. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00763
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |