Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

04/14/2010

Applicant:

6TH AVENUE TITLE SERVICES LLC

Description:

AZ Auto license fire inspection.

Outstanding Inspections

Case Number: T10FR00746
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/14/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/14/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
04/14/2010 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire
04/14/2010 VIOL - COMPRESSED GASES JLOYA Violation TFC 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel. *** Secure gas cylinder in an approved manner to avoid accidental dislodgment.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00746
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/28/2010 INSP - REINSPECTION JLOYA Approved All violations abated.