Case: T10FR00705
Case Details
Entered Date:
04/07/2010
Applicant:
ROBLES JESUS A
Description:
Springpedic mattress factory fire inspection.
Outstanding Inspections
Case Number: T10FR00705
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2010 | VIOL - ADMINISTRATION | JLOYA | Violation | Please provide a copy of your Certificate of Occupancy [C of O] upon re-inspection. |
| 04/07/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 304.2 - Storage. Storage of combustible rubbish shall not produce conditions that will create a nuisance or a hazard to the public health, safety or welfare. |
| 04/07/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. |
| 04/07/2010 | VIOL - PRECAUTION AGAINST FIRE | JLOYA | Violation | 313.1 Fueled equipment. Fueled equipment, including but not limited to motorcycles, mopeds, lawn-care equipment and portable cooking equipment, shall not be stored, operated or repaired within a building. |
| 04/07/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring. |
| 04/07/2010 | VIOL - BUILDING SVCS & SYSTEMS | JLOYA | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. |
| 04/07/2010 | VIOL - FIRE PROTECTION SYSTEMS | JLOYA | Violation | TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00705
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2010 | INSP - FULL | JLOYA | Approved | Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________ |
| 04/23/2010 | INSP - REINSPECTION | JLOYA | Approved | All violations abated. |