Target 4/6/10

Outstanding Inspections

Case Number: T10FR00703
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
04/07/2010 VIOL - PRECAUTION AGAINST FIRE MPURSLEY Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
04/07/2010 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____Place appropriate address numbers on building
04/07/2010 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical outlet
04/07/2010 VIOL - FIRE RESIST.RATED CONST MPURSLEY Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile
04/07/2010 VIOL - FIRE PROTECTION SYSTEMS MPURSLEY Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained. 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. _____Remove storage over tool cage
04/07/2010 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00703
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/19/2010 INSP - REINSPECTION MPursley Approved All corrections made 5/18/10