Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/05/2010

Applicant:

TACO BELL CORP

Description:

Taco Bell 4/2/10

Outstanding Inspections

Case Number: T10FR00689
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
04/05/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00689
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/21/2010 COMPL - REINSPECTION MPursley Approved All corrections made 4/20/10