Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/31/2010

Applicant:

CASA MOLINA INC

Description:

Inspection

Outstanding Inspections

Case Number: T10FR00684
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 25
End Date Description Inspector Results Comments
03/31/2010 VIOL - PRECAUTION AGAINST FIRE TKNAPP Correction Required 315.2.1 Storage height in stockroom.
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 603.2 Chimney at water heater in storage room.
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 Electrical wiring for fountain on patio.
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 Multiplug adapters
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cord
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cords
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.5 Extension cords on patio.
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 J box cover
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open junction box near ice maker.
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open junction box.
03/31/2010 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 Open wiring splice in freezer.
03/31/2010 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11 Appliances shall be located 6" under edge of hood.
03/31/2010 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.1 Hood system shall be operated when equipment is used.
03/31/2010 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.2 Grease filters shall be in place.
03/31/2010 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.3 Hood system shall be cleaned.
03/31/2010 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.6.4 Hood systems shall be inspected at least every six months.
03/31/2010 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 904.11.7 Fryer shall be separated from grill unit.
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 Wrought iron door at SW patio exit.
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.9 Panic hardware at SW patio exit door.
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.9 South exit door from bar shall be equipped with panic hardware.
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 Emergency light installation
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.5 Emergency lights
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.2 Egress from NE patio exit.
03/31/2010 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1028.4 Exit sign installation
03/31/2010 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.5.3 Secure compressed gas cylinders

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00684
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/11/2010 INSP - FULL TKNAPP Approved