Case: T10FR00684
Case Details
Entered Date:
03/31/2010
Applicant:
CASA MOLINA INC
Description:
Inspection
Outstanding Inspections
Case Number: T10FR00684
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 25
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2010 | VIOL - PRECAUTION AGAINST FIRE | TKNAPP | Correction Required | 315.2.1 Storage height in stockroom. |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 603.2 Chimney at water heater in storage room. |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 Electrical wiring for fountain on patio. |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 Multiplug adapters |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cord |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.5 Extension cords on patio. |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 J box cover |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Open junction box near ice maker. |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Open junction box. |
03/31/2010 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 Open wiring splice in freezer. |
03/31/2010 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11 Appliances shall be located 6" under edge of hood. |
03/31/2010 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.1 Hood system shall be operated when equipment is used. |
03/31/2010 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.2 Grease filters shall be in place. |
03/31/2010 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.3 Hood system shall be cleaned. |
03/31/2010 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.6.4 Hood systems shall be inspected at least every six months. |
03/31/2010 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 904.11.7 Fryer shall be separated from grill unit. |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 Wrought iron door at SW patio exit. |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.9 Panic hardware at SW patio exit door. |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.9 South exit door from bar shall be equipped with panic hardware. |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency light installation |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.5 Emergency lights |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.2 Egress from NE patio exit. |
03/31/2010 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1028.4 Exit sign installation |
03/31/2010 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.5.3 Secure compressed gas cylinders |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00684
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2010 | INSP - FULL | TKNAPP | Approved |