Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/30/2010

Applicant:

SMITHS FOOD & DRUG CENTERS INC

Description:

902 w Irvington Wells fargo fire inspection.

Outstanding Inspections

Case Number: T10FR00679
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
03/30/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6 - Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00679
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/30/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/15/2010 INSP - REINSPECTION JLOYA Approved All violations abated.