Description:

Acadamy of Ballet 3/17/10

Outstanding Inspections

Case Number: T10FR00660
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
03/25/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the ---- egress door, as bolt lock of any kind are not permitted
03/25/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1011.1 Where required An approved exit sign shall mark exits and exit access doors and be readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs, in cases where the exit or the path of egress travel is not immediately visible to the occupants; Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1. Exit signs are not required in rooms or areas that require only one exit or exit access. 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official. _____Place exit signs appropriately
03/25/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00660
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/16/2010 INSP - REINSPECTION MPursley Approved All corrections made 4/15/10