Description:

PSI Travel 3/16/10

Outstanding Inspections

Case Number: T10FR00658
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
VIOL - PRECAUTION AGAINST FIRE None Not Inspected
03/25/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
03/25/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____Place sign on outside of door, "This Door Blocked"
03/25/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. _____ Service and tag or remove all portable fire extinguishers in order to meet code standards
03/25/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. _____Maintain minimum aisle width

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00658
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/01/2010 INSP - REINSPECTION MPursley Approved All corrections made 4/1/10