Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/24/2010

Applicant:

ABS SW INVESTOR LLC

Description:

Albertsons 3/22/10

Outstanding Inspections

Case Number: T10FR00655
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
03/25/2010 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. 315.2.3 Equipment rooms Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. _____Keep mechanical room free of storage.
03/25/2010 VIOL - FIRE SERVICE FEATURES MPursley Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ____Keep riser area clear
03/25/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Place back on fan and secure wiring 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code. 605.4.1 Power tap design Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. ____Use approved multi-plug adaptors 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips. 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____ Place approved cover(s) over the electrical boxes
03/25/2010 VIOL - FIRE RESIST.RATED CONST MPursley Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile
03/25/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained.
03/25/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Test and keep generator log. 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the recieving egress doors, as bolt lock of any kind are not permitted 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). 3. No additional locks or latches shall be added _____Have panic hardware repaired

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00655
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/29/2010 INSP - REINSPECTION MPursley Approved All corrections made 4/29/10