Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/11/2010

Applicant:

GALINDO LUIS A & LORENA M JT/RS

Description:

Arisona Sonora fire inspection.

Outstanding Inspections

Case Number: T10FR00558
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
03/11/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
03/11/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
03/11/2010 VIOL - HAZARDOUS MATERIALS,GEN JLOYA Violation 2703.3 Release of hazardous materials. Hazardous materials in any quantity shall not be released into a sewer, storm drain, ditch, drainage canal, creek, stream, river, lake or tidal waterway or on the ground, sidewalk, street, highway or into the atmosphere. ___ Provide secondary containment for oil collection container.
03/11/2010 VIOL - COMPRESSED GASES JLOYA Violation 3803.2.1 Portable containers. Portable LP-gas containers, as defined in NFPA 58, shall not be used in buildings.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00558
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/11/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/15/2010 INSP - REINSPECTION JLOYA Approved All violations abated.