Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/01/2010

Applicant:

TUCSON TALLOW CO INC

Description:

Full Fire Prevention Inspection. Balvino Hurtado 887-0440

Outstanding Inspections

Case Number: T10FR00411
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
03/01/2010 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 310.3 “No Smoking” signs. The fire code official is authorized to order the posting of “No Smoking” signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required “No Smoking” signs shall be approved. _____1. Post "NO SMOKING" signs in the shop and in all processing areas.
03/01/2010 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. _____1. Address numbers shall be in accordance with Pima County address display requirements. NOTE: See attached requirements for more information. NOTE: Cut bushes away from where the address will be posted.
03/01/2010 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required IFC 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. _____1. A fire department lock box with a gate key inside shall be installed on or near the entrance gate for fire department access into the property. NOTE: See attached order form.
03/01/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the cube adapter used under the break room table by the microwave. NOTE: Replace it with a fused power-strip plugged directly into an electrical outlet.
03/01/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service, test, tag and mount all portable fire extinguishers. NOTE: Store all extra portable fire extinguishers in one location. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
03/01/2010 VIOL - HAZARDOUS MATERIALS,GEN JBURGE Correction Required IFC 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. IFC 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: COMPRESSED GAS. _____1. Label all tanks and containers to identify their contents.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00411
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/01/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.