Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/24/2010

Applicant:

BELLRICH LLC

Description:

Proline Graphics 2/23/10

Outstanding Inspections

Case Number: T10FR00400
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
VIOL - FIRE SERVICE FEATURES None Not Inspected
02/24/2010 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep dryer clear.
02/24/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background
02/24/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____Repair damaged power cord.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00400
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/30/2010 COMPL - REINSPECTION MPURSLEY Approved All corrections made 3/30/10