Case: T10FR00400
Case Details
Entered Date:
02/24/2010
Applicant:
BELLRICH LLC
Description:
Proline Graphics 2/23/10
Outstanding Inspections
Case Number: T10FR00400
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| VIOL - FIRE SERVICE FEATURES | None | Not Inspected | ||
| 02/24/2010 | VIOL - PRECAUTION AGAINST FIRE | MPursley | Correction Required | 315.2 Storage in buildings Storage of combustible materials shall be orderly. Storage shall be separated from heaters or heating devices so that ignition cannot occur. ____Keep dryer clear. |
| 02/24/2010 | VIOL - BUILDING SVCS & SYSTEMS | MPursley | Correction Required | 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background |
| 02/24/2010 | VIOL - BUILDING SVCS & SYSTEMS | MPursley | Correction Required | 605.6 Unapproved conditions Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers. _____Repair damaged power cord. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00400
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2010 | COMPL - REINSPECTION | MPURSLEY | Approved | All corrections made 3/30/10 |