Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/24/2010

Applicant:

BELLRICH LLC

Description:

Settlemeyer LLC. 2/23/10

Outstanding Inspections

Case Number: T10FR00397
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
02/24/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Place electrical blanks in any open void spaces in your electrical panel
02/24/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-keyed lock and replace with an approved locking device such as, thumb turn lock or panic hardware 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" visibly above your main egress door.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00397
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/30/2010 COMPL - REINSPECTION MPURSLEY Approved All corrections made 3/30/10