Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/23/2010

Applicant:

BELLRICH LLC

Description:

T&C Pet Grooming 2/22/10

Outstanding Inspections

Case Number: T10FR00391
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
02/23/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.4.1 Power tap design Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. _____Remove non approved multi plug adaptors. 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters.
02/23/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained. Maintain or remove non required fire extinguishers.
02/23/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your back door.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00391
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/06/2010 COMPL - REINSPECTION MPursley Approved All corrections made 4/5/10