Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/16/2010

Applicant:

BELLRICH LLC

Description:

Frontier Asset Protection 2/16/10

Outstanding Inspections

Case Number: T10FR00366
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
02/16/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters.
02/16/2010 VIOL - FIRE RESIST.RATED CONST MPursley Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix and repair all openings or holes in the ceiling
02/16/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained.
02/16/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-keyed lock and replace with an approved locking device such as, thumb turn lock or panic hardware

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00366
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/18/2010 COMPL - REINSPECTION MPursley Approved All corrections made 3/16/10