Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

02/10/2010

Applicant:

FPI LLC AZ

Description:

Suppercuts 2/8/10

Outstanding Inspections

Case Number: T10FR00339
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
02/10/2010 VIOL - FIRE RESIST.RATED CONST MPURSLEY Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00339
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/23/2010 COMPL - REINSPECTION MPursley Approved All corrections made 2/22/10