Description:

Holiday market fire inspection.

Outstanding Inspections

Case Number: T10FR00270
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
02/02/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
02/02/2010 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.
02/02/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
02/02/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
02/02/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following e2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch high on a contrasting background exists.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00270
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/17/2010 INSP - REINSPECTION JLOYA Approved All violations abated.