Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

01/28/2010

Applicant:

CITY OF TUCSON

Description:

MAITS - FIRE CODE COMPLIANCE INSPECTION

Outstanding Inspections

Case Number: T10FR00232
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
01/28/2010 VIOL - BUILDING SVCS & SYSTEMS RHEATH Correction Required Two exits signs did not function properly when tested. Repair the units. International Fire Code 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator.