Case Number: T10FR00228
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
02/04/2010 INSP - FULL BCORRALE Continued On 02/04/2010, a fire prevention inspection was conducted at Broadway Proper, please correct the following Tucson fire code violations. All code references are from the 2006 International Fire Code, with local modifications.
02/09/2010 VIOL - FIRE SERVICE FEATURES BCORRALE Continued Unable to see Riser sign from walkway. (Courtyard) 510.1 Identification ___Move sign to face walkway.
02/09/2010 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Continued Provide pull station training for kitchen employees. 901.6 Inspection, testing and maintenance. ___Provide training for kitchen staff.
02/09/2010 VIOL - FIRE PROTECTION SYSTEMS BCORRALE Continued Sprinkler heads painted over. 901.6 Inspection, testing and maintenance. ____Repair/replace heads.
02/09/2010 VIOL - MEANS OF EGRESS BCORRALE Continued Exit sign out of service. (Rm. 1160) 1027.5 Illumination emergency power. ____Repair/replace exit sign to full working order.