Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/28/2010

Applicant:

BELLRICH LLC

Description:

RxO2 1/27/10

Outstanding Inspections

Case Number: T10FR00222
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
01/28/2010 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
01/28/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire protection systems and equipment shall be inspected, tested and maintained.
01/28/2010 VIOL - COMPRESSED GASES MPursley Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00222
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/23/2010 COMPL - REINSPECTION MPursley Approved All corrections made 2/22/10