Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/28/2010

Applicant:

BELLRICH LLC

Description:

ARS 1/27/10

Outstanding Inspections

Case Number: T10FR00221
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
01/28/2010 VIOL - PRECAUTION AGAINST FIRE MPursley Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
01/28/2010 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used… Electrical blanks shall be placed in all open spaces within any electrical panel or box. _____ Place electrical blanks in any open void spaces in your electrical panel
01/28/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your back door.
01/28/2010 VIOL - COMPRESSED GASES MPursley Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00221
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/17/2010 COMPL - REINSPECTION MPURSLEY Approved All corrections made 2/17/10