Case: T10FR00136
Case Details
Entered Date:
01/25/2010
Applicant:
CITY OF TUCSON
Description:
Maitts 6 month
Outstanding Inspections
Case Number: T10FR00136
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - LIFE SAFETY | None | Not Inspected | ||
01/25/2010 | VIOL - PRECAUTION AGAINST FIRE | gdauria | Violation | TFC 315.2.1 Ceiling clearance. Music Hall Storage shall be maintained a minimum of 18 inches below sprinkler head deflectors. Remove stored equipment from beneath stairwells on first level. |
01/25/2010 | VIOL - FIRE SERVICE FEATURES | gdauria | Violation | TFC 506.1 Key Boxes. Arena/N x-Hall Maint. Rm. Install approved TFD lockbox or padlock at gate to FD Riser. |
01/25/2010 | VIOL - FIRE SERVICE FEATURES | gdauria | Violation | TFC 510 FD Access to Equip. (Signage)- Arena Storge Mezzanine Install Fire Sprinkler Riser Sign @ ladder access; south end, by elevators |
01/25/2010 | VIOL - FIRE SERVICE FEATURES | gdauria | Violation | TFC 510 FD Access to Equip. (Signage)- Arena x-hall Mech Rm Install Fire Sprinkler Riser Sign @ entry |
01/25/2010 | VIOL - FIRE SERVICE FEATURES | gdauria | Violation | TFC 510 FD Access to Equip. (Signage)- Arena, Womens Bath Rm Install Fire Sprinkler Riser Sign @ entry |
01/25/2010 | VIOL - FIRE RESIST.RATED CONST | gdauria | Violation | TFC 703.1 Fire Resistive Const. -Ceiling Tiles (several areas) Replace missing tiles @ north x-hall kitchen, Main Kitchen (several), Arena concourse (by concessions), Leo Rich (spot booth), Music Hall (@ Women's RR 1st floor, bakstage x2) |
01/25/2010 | VIOL - FIRE RESIST.RATED CONST | gdauria | Violation | TFC 703.2 Opening protectives. - North x-hall Repair required door closure (NW corner) |
01/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | gdauria | Violation | TFC 901.6 Inspection, testing, maint. Main Kitchen(Hood System) Have hood extinguishing system tested and tagged asap. (was due 12/2009) |
01/25/2010 | VIOL - FIRE PROTECTION SYSTEMS | gdauria | Violation | TFC 901.8 Removal of Equipment - x-halls Remove hose from fire hose cabints in x-halls or have tested annually |
01/25/2010 | VIOL - MEANS OF EGRESS | gdauria | Violation | TFC 1008 Doors. North Meeting Rooms "Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials." Clearly mark doorways @ drapes @north exits |
01/25/2010 | VIOL - MEANS OF EGRESS | gdauria | Violation | TFC 1008.1.8.3 Locks and latches. - North x-hall Kitchen install a thumb bolt @ the exit to the exterior |
01/25/2010 | VIOL - COMPRESSED GASES | gdauria | Violation | TFC 3003.5.3 Securing compressed gas containers, - Dock area All cylinders (emty or not) shall be secured |