Maitts 6 month

Outstanding Inspections

Case Number: T10FR00136
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
INSP - LIFE SAFETY None Not Inspected
01/25/2010 VIOL - PRECAUTION AGAINST FIRE gdauria Violation TFC 315.2.1 Ceiling clearance. Music Hall Storage shall be maintained a minimum of 18 inches below sprinkler head deflectors. Remove stored equipment from beneath stairwells on first level.
01/25/2010 VIOL - FIRE SERVICE FEATURES gdauria Violation TFC 506.1 Key Boxes. Arena/N x-Hall Maint. Rm. Install approved TFD lockbox or padlock at gate to FD Riser.
01/25/2010 VIOL - FIRE SERVICE FEATURES gdauria Violation TFC 510 FD Access to Equip. (Signage)- Arena Storge Mezzanine Install Fire Sprinkler Riser Sign @ ladder access; south end, by elevators
01/25/2010 VIOL - FIRE SERVICE FEATURES gdauria Violation TFC 510 FD Access to Equip. (Signage)- Arena x-hall Mech Rm Install Fire Sprinkler Riser Sign @ entry
01/25/2010 VIOL - FIRE SERVICE FEATURES gdauria Violation TFC 510 FD Access to Equip. (Signage)- Arena, Womens Bath Rm Install Fire Sprinkler Riser Sign @ entry
01/25/2010 VIOL - FIRE RESIST.RATED CONST gdauria Violation TFC 703.1 Fire Resistive Const. -Ceiling Tiles (several areas) Replace missing tiles @ north x-hall kitchen, Main Kitchen (several), Arena concourse (by concessions), Leo Rich (spot booth), Music Hall (@ Women's RR 1st floor, bakstage x2)
01/25/2010 VIOL - FIRE RESIST.RATED CONST gdauria Violation TFC 703.2 Opening protectives. - North x-hall Repair required door closure (NW corner)
01/25/2010 VIOL - FIRE PROTECTION SYSTEMS gdauria Violation TFC 901.6 Inspection, testing, maint. Main Kitchen(Hood System) Have hood extinguishing system tested and tagged asap. (was due 12/2009)
01/25/2010 VIOL - FIRE PROTECTION SYSTEMS gdauria Violation TFC 901.8 Removal of Equipment - x-halls Remove hose from fire hose cabints in x-halls or have tested annually
01/25/2010 VIOL - MEANS OF EGRESS gdauria Violation TFC 1008 Doors. North Meeting Rooms "Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials." Clearly mark doorways @ drapes @north exits
01/25/2010 VIOL - MEANS OF EGRESS gdauria Violation TFC 1008.1.8.3 Locks and latches. - North x-hall Kitchen install a thumb bolt @ the exit to the exterior
01/25/2010 VIOL - COMPRESSED GASES gdauria Violation TFC 3003.5.3 Securing compressed gas containers, - Dock area All cylinders (emty or not) shall be secured