Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/20/2010

Applicant:

TUCSON PLACE PARTNERS LLC

Description:

Full Fire Prevention Inspection. Quinn Nguyen 888-1248

Outstanding Inspections

Case Number: T10FR00111
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
01/20/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove all storage located in front of the electrical service equipment in the back room.
01/20/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove the extension cord and cube adapter located in the back room. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
01/20/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the portable fire extinguisher or replace it with a new one.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00111
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/17/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.