Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T10FR00059
Case Details
Entered Date:
01/12/2010
Applicant:
CENTRO NP HOLDINGS 1 SPE LLC
Description:
Full Fire Prevention Inspection. Rusty Conrad 887-7971
Outstanding Inspections
Case Number: T10FR00059
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and test the fire alarm system and provide the inspection report. _____2. Align the hood extinguishing system nozzles to properly cover the cooking equipment. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
01/12/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the broken emergency lighting unit located by the exit door near the restrooms. _____2. Repair or replace the broken emergency lighting unit located above the northeast casheer station. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00059
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |