Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/08/2010

Applicant:

ZEDEDA PAUL M & GLORIA R TR

Description:

Santa Rita Suds fire inspection.

Outstanding Inspections

Case Number: T10FR00042
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
01/08/2010 INSP - FULL JLOYA Violation Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
01/08/2010 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00042
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
01/26/2010 INSP - REINSPECTION JLOYA Approved Alll violations abated.