Case Details

Status:

COMPLIAN

Type:

RESIDENTIAL FIRE
Address:

Entered Date:

12/01/2010

Applicant:

PROPST FAMILY REVOCABLE TR (THE)

Description:

House Fire

Case Violations

Case Number: T10DV08655
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Violations: 3
Violation Date Code Statue
12/22/2010 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
12/22/2010 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.
12/22/2010 UDC, Sec. 10.2.3. COMPLIANCE REVIEW, EXISTING DEVELOPMENT Any land used or occupied; any site improvement, modification, or construction started; any existing use or structure expanded, reconstructed, changed, or otherwise altered; and any land divided into multiple parcels without certification of compliance with the provisions of the UDC through a zoning review process is considered a violation of the UDC. Enforcement of violations shall be in accordance with Section 10.4, Penalties and Remedies.

Outstanding Inspections

Case Number: T10DV08655
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
12/09/2010 NPO(HC)-COOLING HLOPEZ Item closed
12/23/2010 NPO(EL)-MAIN/PANEL/SUB/DISCONT HLOPEZ Notice of violation
12/23/2010 NPO(EL)-WIRING/SWITCH/OUTLT/FX HLOPEZ Notice of violation
12/23/2010 NPO(PL)-PLUMBING SYSTEM & FX HLOPEZ Notice of violation
12/23/2010 NPO(PL)-WATER HEATERS HLOPEZ Notice of violation
12/23/2010 NPO(HC)-NO VENTILATION HLOPEZ Notice of violation
12/23/2010 NPO(HC)-HEATING & VENTILATION HLOPEZ Notice of violation
12/23/2010 NPO - WORK WITHOUT PERMIT HLOPEZ Notice of violation
12/23/2010 NPO - INT. BUILDING MAINTENANC HLOPEZ Notice of violation

Completed Inspections

Case Status: COMPLIAN
Case Number: T10DV08655
Case Description: RESIDENTIAL FIRE
Total Completed Inspections - 3
End Date Description Inspector Results Comments
12/01/2010 INSP - INITIAL CODE ENFORCMENT HLOPEZ Approved EMERGENCY CALL OUT NOV ISSUED, HAND DELIVERED & SIGNED, 7 DAY FW/UP EXTENSIVE NOTES, SEE CASE PACKET FOR DETAILS.
12/01/2010 INSP - INITIAL CODE ENFORCMENT GGOODMAN Approved FURNACE TAGGED IN JUNE 2010. VENT IMPROPERLY INSTALLED. COUCH PUSHED IN FRONT OF RETURN AIR GRILLE. VENT ABOVE ROOF HAS CAP INSTALLED AT ROOF LINE. DEBRIS CLOGGED VENT PIPE AT ROOF. FURNACE ROOM DRYWALL FALLING OFF FROM THE CEILING NOT SEALED AT EDGES. HOLES IN WALL WHERE HOT WATER HEATER WATER LINES ENTER THE WALL. DRAIN LINE TO HOT WATER HEATER IS, PVC AND NOT DRAINING TO A PAN. HOT WATER HEATER TAGGED BY SW GAS. PLY SHEATHING CHARRED AROUND VENT CAP.
12/09/2010 INSP - FOLLOW UP CODE ENFORCE HLOPEZ Approved COMPLIANCE INSP/HEATING SYS Site inspection, insp. received complaints regarding electrical sys. new heating appliance installed, installation not to code, turns out unlicensed contactor talked owner into replacing furnace permit & inspection required. insp. of elect. sys. open grounds, GFIC lacking in kitchen & bth rm, 2 wire sys. w/o/p carport & porch converted into habitable space, window openings in rm not to code. laundry rm also added w/elect & plumbing. nov to be sent for new issues

Completed Activity Special Conditions

Case Description - RESIDENTIAL FIRE
Case Number - T10DV08655
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 10
Date Name
12/22/2010 CONTACTED BY PHONE
12/23/2010 CONTACTED BY MAILING
05/05/2011 CONTACTED BY EMAIL
12/02/2010 NOTICE OF VIOLATION ISSUED
06/02/2011 VIOLATION CLOSED
04/05/2011 RESEARCH
12/01/2010 8-5 CITY COMM EMERGENCY
04/06/2011 REINSPECTION FEE - FIRST
11/01/2011 REINSP FEE - PAID IN FULL
12/22/2010 NOTICE OF VIOLATION ISSUED

Documents

File Name Document Type  
NOV 12.01.10.PDF DOCUMENTS VIEW