Case: T10DV05292
Case Details
Entered Date:
08/10/2010
Applicant:
MARKUS SOKSER TR 1/2 & MARGARET E. MONZ 1/2
Description:
New windows, and an AC split system installed without historic review.
Case Violations
Case Number: T10DV05292
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Violations: 3
Violation Date | Code Statue |
---|---|
09/07/2010 | T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe. |
09/07/2010 | UDC, Sec. 10.2.3. COMPLIANCE REVIEW, EXISTING DEVELOPMENT Any land used or occupied; any site improvement, modification, or construction started; any existing use or structure expanded, reconstructed, changed, or otherwise altered; and any land divided into multiple parcels without certification of compliance with the provisions of the UDC through a zoning review process is considered a violation of the UDC. Enforcement of violations shall be in accordance with Section 10.4, Penalties and Remedies. |
09/07/2010 | T.C. Ch. 16, Sec. 16-11(d) MECHANICAL EQUIPMENT. All mechanical equipment and appliances shall be properly installed, maintained in a safe, working, operating condition, and shall be free of any defect that impairs operability. |
Outstanding Inspections
Case Number: T10DV05292
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2010 | NPO - REFUSE/TRASH/DEBRIS | JVALDEZ | Follow-up inspection | |
11/10/2010 | NPO - WORK WITHOUT PERMIT | JVALDEZ | Follow-up inspection |
Completed Inspections
Case Status: COMPLIAN
Case Number: T10DV05292
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2010 | INSP - INITIAL CODE ENFORCMENT | JVALDEZ | Approved | THREE SANYO MINI-SPLIT AIR CONDITIONER HEAT PUMPS HAVE BEEN INSTALLED WITHOUT PERMITS. ONE PANEL BOARD WAS INSTALLED WITH OUT PERMITS. THE PANEL BOARD IS CONNECTED DIRECT WITH NO MEANS OF DISCONNECT. THE INTERIOR OF THE PANEL BOARD HAS OPEN SPACES WITH NO BLANK COVERS. THERE ARE EXTERIOR NEW CIRCUITS COMING FROM THE PANEL. NO PANEL SCHEDULE. NEW WINDOWS HAVE BEEN INSTALLED WITHOUT HISTORICAL REVIEW, GAS WATER HEATERS HAVE NO PROTECTIVE ENCLOSURES. |
11/10/2010 | INSP - FOLLOW UP CODE ENFORCE | JVALDEZ | Approved | ENCLOSURES FOR GAS WATER HEATERS WEE INSTALLED, PERMIT T10CM02681 IN ISSUED STATED. SCHEDULE FOLLOW INSPECTION FOR 3-23-2011 |
Completed Activity Special Conditions
Case Description - WORK WITHOUT PERMITS-RESIDENTL
Case Number - T10DV05292
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
Date | Name |
09/07/2010 | CONTACTED BY PHONE |
09/08/2010 | CONTACTED BY MAILING |
09/08/2010 | NOTICE OF VIOLATION ISSUED |
04/03/2012 | VIOLATION CLOSED |