Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING

Entered Date:

06/25/2010

Applicant:

VILLAGE GREEN HOMEOWNERS ASSN

Description:

Outlet in the kitchen area of clubhouse shot out flames when appliance was unplugged. Need to call the complaintant to gain access to the clubhouse.

Case Violations

Case Number: T10DV04184
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 1
Violation Date Code Statue
07/09/2010 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.

Outstanding Inspections

Case Number: T10DV04184
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
07/25/2010 NPO(EL)-WIRING/SWITCH/OUTLT/FX RDIAZ Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T10DV04184
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
06/30/2010 INSP - INITIAL CODE ENFORCMENT RDIAZ Approved 6/30/10 11:30AM, INSPECTION OF THE CLUB HOUSE WAS MADE IN THE AREA OF WHICH THE COMPLAINT STATED. IT WAS NOTED THAT TWO MICRO-WAVE OVENS ARE IN THE KITCHEN NON GFI OUTLETS. NOTICE OF VIOLATION WITH 30 DAYS TO ABATE. REPAIR AND OR REPLACE BY QUILIFIED ELECTRICIAN.
07/25/2010 INSP - FOLLOW UP CODE ENFORCE RDIAZ Approved 7/25/10 A GFI ELECTRICIAL OUTLET HAS BEEN INSTALLED IN THE KITCHEN AREA OF THE CLUB HOUSE By A QUALIFIED ELECTRICIAN. VIOLATION HAS BEEN ABATED CLOSE CASE.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T10DV04184
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date Name
08/11/2010 CONTACTED BY MAILING
08/11/2010 NOTICE OF VIOLATION ISSUED
08/19/2010 VIOLATION CLOSED