Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/31/2009

Applicant:

JUMBO PROPERTY GROUP LLC

Description:

A World of Tile Initial inspection 12/29/09.

Outstanding Inspections

Case Number: T09FR03918
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/31/2009 VIOL - BUILDING SVCS & SYSTEMS MPursley Correction Required 605.5 Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring. Cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ All extension cords shall be removed and/or replace with approved fused power strips
12/31/2009 VIOL - MEANS OF EGRESS MPursley Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards Exit signs shall be internally or externally illuminated. The face of an exit sign 1027.3 Exit sign illumination. illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards 1011.1 Where required An approved exit sign shall mark exits and exit access doors and be readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs, in cases where the exit or the path of egress travel is not immediately visible to the occupants; Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1. Exit signs are not required in rooms or areas that require only one exit or exit access. 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official. _____Place exit sign for back hall. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your back exit.
12/31/2009 VIOL - COMPRESSED GASES MPursley Correction Required 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ Properly secure all compressed gas cylinders at all times

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03918
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/22/2010 INSP - REINSPECTION MPursley Approved All corrections made 2/19/10