Case: T09FR03907
Case Details
Entered Date:
12/29/2009
Applicant:
SPIRIT MASTER FUNDING LLC
Description:
Full Fire Prevention Inspection Building Rep: Monica Sanchez Phone # 888-7444
Outstanding Inspections
Case Number: T09FR03907
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2009 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
| 12/29/2009 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. _____ The sprinkler head in the restroom is currently being obstructed and shall either be moved to a better location or the door obstructing the head shall be removed or altered to make the sprikler operable. |
| 12/29/2009 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. ______ Remove the drop bar system from your rear egress door. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ___ ___ ___ ___________________ Passed on: ________ (Joseph P. Longo) |