Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/29/2009

Applicant:

BROADWAY POWER CENTER GROUP LLC

Description:

Full inspection done 12/29/09; Jim Harrell - owner; 886-5524; "B" occupancy;

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03901
Case Description: INSPECTION
Total Completed Inspections - 9
End Date Description Inspector Results Comments
12/29/2009 VIOL - LIQUID PETROLEUM GASES BCOBB Approved LPG tank and heater: IFC603.4 [and NFPA 58 - 6.17.8] _____ Remove heater. This is the second time you have been told this [see report T07FR00948 Greenleaf] - If this is found again you will be given a citation. Thank you,
12/29/2009 VIOL - MEANS OF EGRESS BCOBB Approved Exit access, exit, and discharge path blocked: 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. ______ Clear exit path and keep it clear [36" minimum] Thank you,
12/29/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Sprinkler system: 903.5 Testing and maintenance. Sprinkler systems shall be tested and maintained in accordance with Section 901. _______ System to be tested, and tagged annually. [All deficiencies abated, and a copy of the report to be on the premises]
12/29/2009 VIOL - FIRE PROTECTION SYSTEMS BCOBB Approved Extinguishers not tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code.
12/29/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Open space in electrical panel: TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _____Place an approved "blank" in the space.
12/29/2009 VIOL - BUILDING SVCS & SYSTEMS BCOBB Approved Tape on breaker: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. _______ Remove tape from breakers.
12/29/2009 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Housekeeping: TFC 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. _____ Clean up as much as possible....
12/29/2009 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head.
01/20/2010 INSP - FULL BCOBB Approved