Status:

COMPLETE

Type:

INSPECTION

Entered Date:

12/29/2009

Applicant:

BROADWAY POWER CENTER GROUP LLC

Description:

Full inspection done 12/23/2009; Harry Paulus - 296-1517 [owner]; "M" occupancy;

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03898
Case Description: INSPECTION
Total Completed Inspections - 3
End Date Description Inspector Results Comments
12/29/2009 VIOL - FIRE SERVICE FEATURES BCOBB Approved Jammed back door: TFC 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. ______ Unjam door - [Done 12/23/09]
12/29/2009 VIOL - PRECAUTION AGAINST FIRE BCOBB Approved Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head. Thank you,
12/29/2009 INSP - FULL BCOBB Approved Please correct the following Tucson Fire Code violations: