Case: T09FR03851
Case Details
Entered Date:
12/23/2009
Applicant:
ADOBE PLASTIC SURGERY P C
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T09FR03851
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 1.) TFC 605.4.2 POWER STRIPS IN OFFICE MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET NOT "PIGGY BACKED". |
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 2.) TFC 605.5 EXTENSION CORD POWERING THE COPY MACHINE IN O.R. CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 3.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN O.R. ABOVE NURSES DESK. |
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 4.) TFC 1008.1.8 EGRESS DOORS IN RESEARCH BUILDING MUST HAVE THUMB TURN LATCHES ON INSIDE OF DOORS. REMOVE DOUBLE DEAD BOLT LOCKS IN 3 LOCATIONS, 2 IN RECORDS AREA AND 1 BY THE KITCHEN. |
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 5.) TFC 1008.1.8.3 THE MAIN EXIT DOOR FROM THE RESEARCH BUILDING MUST HAVE 1" LETTERED SIGN STATING " THIS DOOR TO REMAIN UNLOCKED WHILE THE BUILDING IS OCCUPIED". |
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 6.) TFC 901.6 RE-SECURE SMOKE DETECTOR TO CEILING IN RECORDS AREA OF RESEARCH BUILDING. |
12/23/2009 | INSP - FULL | RSPANGLE | Violation | 7.) TFC 901.6.2 A COPY OF ANNUAL SPRINKLER SYSTEM REPORT MUST BE SUBMITTED UPON RE-INSPECTION. |