Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/16/2009

Applicant:

PEP PROPERTIES INC

Description:

Pep Boy's fire inspection.

Outstanding Inspections

Case Number: T09FR03782
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/16/2009 VIOL - PRECAUTION AGAINST FIRE JLOYA Violation 315.2.1 - Ceiling clearance. Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings. ___ Tire room.
12/16/2009 VIOL - FIRE SERVICE FEATURES JLOYA Violation 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. Address numbers shall be in accordance with Pima County address display requirements.
12/16/2009 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
12/16/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
12/16/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
12/16/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____Remove locking mechanisms from emergancy exit doors.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03782
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/16/2009 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
01/07/2010 INSP - REINSPECTION JLOYA Approved All violations abated.